Showing posts with label 400kV Line. Show all posts
Showing posts with label 400kV Line. Show all posts

Saturday, October 8, 2011

National Energy Conference 2011

The 2nd Annual National Energy Conference started in 4th to 6th of this week, I attended the Wednesday 5th event and the presentations were impressive.
There was a good number of exhibitors were in attendance to show their products in in the energy sector. The public attendance was good, though not many were there on that day.
The 3-day event was at KICC (Kenyatta International Conference Centre).



▲The Power Technics stand was the most impressive, they mounted a VAWT (Vertical Axis Wind Turbine) which was spinning perfectly. Their people at the stand were also helpful. This was a coincidence because I was on attachment there last year. Good work PTL
Geothermal Development Corporation, GDC had an impressive rig for drilling of steam at a well. This model was detailed and given again that I had gone for attachment there, I understood everything well. The person who modeled this, whoever you are, good work.

Another stand worth the mention was KETRACO-Kenya Electricity Transmission Company, a newly formed government corporation that is in charge of the transmission lines handed over from Kenya Power. The gentlemen who were there to explain were very informed and knew what they were saying. The stand looked presentable with a PC to show a GIS software for designing the transmission line network.

Recommendations
  1. Lake Turkana Wind Power should have been there, that was the primary reason why I attended.
  2. More exhibitors will increase public attendance.
To the event organizers, splendid work, keep up.

Monday, May 24, 2010

Extra High Voltage Systems - 400kV Lines


Nominal Voltage                      400kV
Cicuits per phase                     1
Sub-conductors per phase        2
Span                                      400m
Conductor Name and Size       Moose,54/3.53mm Alluminium  7/3.53mm Steel
Sub-conductor Diameter          3.177cm
Bundle Configuration                Horizontal
Bundle Spacing                       450mm
Interphase Spacing                   11m
Condutor Configuration            Horizontal
Resistance per phase per km at 20degrees 0.0274Ohm
Inductive Reactance per phase per km              0.3321Ohm
Shunt Admittance per phase per km                  3.2983*10-6
Surge Impedance                    282Ohm
Surge Impedance Loading        505MW
Current Carying capacity at 40degrees ambient temperature 900A
Ground Wire                           2Number,7/3.66mm Galvanised Steel
Ground wire height at tower                30.4m
Tower height                           30.4m
Conductor Height at tower           20.75m
Conductor sag at 0degrees           8.39m
Ground wire sag at 0degrees               6.654m
Shielding angle                           10degrees
Suspension string                   23dics,225*145mm
Impulse Flashover voltage                   1550kV

Examples:Sultanpur-Lucknow Line, Obra-kanput Line, Kanpur-Maradnagar Line.