Monday, May 24, 2010
Extra High Voltage Systems - 400kV Lines
Nominal Voltage 400kV
Cicuits per phase 1
Sub-conductors per phase 2
Span 400m
Conductor Name and Size Moose,54/3.53mm Alluminium 7/3.53mm Steel
Sub-conductor Diameter 3.177cm
Bundle Configuration Horizontal
Bundle Spacing 450mm
Interphase Spacing 11m
Condutor Configuration Horizontal
Resistance per phase per km at 20degrees 0.0274Ohm
Inductive Reactance per phase per km 0.3321Ohm
Shunt Admittance per phase per km 3.2983*10-6
Surge Impedance 282Ohm
Surge Impedance Loading 505MW
Current Carying capacity at 40degrees ambient temperature 900A
Ground Wire 2Number,7/3.66mm Galvanised Steel
Ground wire height at tower 30.4m
Tower height 30.4m
Conductor Height at tower 20.75m
Conductor sag at 0degrees 8.39m
Ground wire sag at 0degrees 6.654m
Shielding angle 10degrees
Suspension string 23dics,225*145mm
Impulse Flashover voltage 1550kV
Examples:Sultanpur-Lucknow Line, Obra-kanput Line, Kanpur-Maradnagar Line.